Air Diffusion's FlowBar is an architecturally designed, high capacity linear slot diffuser. It is designed to combine a very high air handling capacity with maximum flexibility and is suitable for either ceiling or sidewall applications. The flexibility of the system can blend into a design or provide contrast with its striking, but simple design. METALAIRE is the flagship brand of Metal Industries Inc., offering a complete line of air distribution and air terminal products. From standard grilles and registers, to its architectural line of Formations® linear slot diffusers, along with a newly released series of displacement diffusers, METALAIRE has the air devices to meet every need.
- FlowBar linear diffuser designed to fit into Armstrong TechZone ceiling grid systems in 4' and 6' nominal widths Slot width is 1' and is available in either high throw (HT) or jet throw (JT) configuration Three border types available - LT (lay-in), NT (narrow tee), and DF (drop face) Adjustable pattern controllers change direction of airflow.
- Overview The SDS linear slot diffuser is designed to satisfy architectural applications that require continuous lengths without compromising air distribution performance. These linear slot diffusers feature fully adjustable, aerodynamic pattern controllers fabricated from extruded aluminum, and are available in a large selection of frame styles.
- Titus FlowBar architectural linear diffuser system maximizes engineering performance without sacrificing aesthetic considerations for the designer. FlowBar's outstanding performance allows higher air flows than conventional linear diffusers. The wide array of slot widths allow for more CFM per linear foot while minimizing noise and pressure loss.
Aerodynamically designed blades provide a tight horizontal pattern that maintains stability even at low airflow rates, making the SDS ideal for VAV applications. Excellent for architectural applications, the SDS has many mounting styles and is available with multiple slot widths and quantities to meet a range of airflow requirements.
- Models
- Supply (SDS)
- Return (SDR)
- Curved supply/return (SDC)
- 4-way Slot Diffuser (SDS4)
- Plenum
- Sloped (SDA)
- Square (SDB)
- Slot Widths
- 1/2 in.
- 3/4 in.
- 1 in.
- 1 1/2 in.
- Slot Quantity
- 1 to 10
- Accessories
- Blank-off strips
- Mitered corner section (MC)
- FlowBar linear diffuser designed to fit into Armstrong TechZone ceiling grid systems in 4' and 6' nominal widths Slot width is 1' and is available in either high throw (HT) or jet throw (JT) configuration Three border types available - LT (lay-in), NT (narrow tee), and DF (drop face) Adjustable pattern controllers change direction of airflow.
- Overview The SDS linear slot diffuser is designed to satisfy architectural applications that require continuous lengths without compromising air distribution performance. These linear slot diffusers feature fully adjustable, aerodynamic pattern controllers fabricated from extruded aluminum, and are available in a large selection of frame styles.
- Titus FlowBar architectural linear diffuser system maximizes engineering performance without sacrificing aesthetic considerations for the designer. FlowBar's outstanding performance allows higher air flows than conventional linear diffusers. The wide array of slot widths allow for more CFM per linear foot while minimizing noise and pressure loss.
Aerodynamically designed blades provide a tight horizontal pattern that maintains stability even at low airflow rates, making the SDS ideal for VAV applications. Excellent for architectural applications, the SDS has many mounting styles and is available with multiple slot widths and quantities to meet a range of airflow requirements.
Construction Options- Models
- Supply (SDS)
- Return (SDR)
- Curved supply/return (SDC)
- 4-way Slot Diffuser (SDS4)
- Plenum
- Sloped (SDA)
- Square (SDB)
- Slot Widths
- 1/2 in.
- 3/4 in.
- 1 in.
- 1 1/2 in.
- Slot Quantity
- 1 to 10
- Accessories
- Blank-off strips
- Mitered corner section (MC)
Model JADJAD
The Polyaire JAD Jet Diffuser is designed for the supply of large air volumes where long throw distances are required. Polyaire Jet Diffusers are used extensively in large areas and high ceiling applications such as Sports Centres, Airports, Entertainment Complexes, Shopping Centres and Industrial areas.
Jet Diffusers are also used for Spot Cooling or Heating and the Jet diffuser can be rotated by 180 degree by adjusting the core, changing the throw pattern from Jet to Diffused Mode.
The Polyaire Jet Diffuser is available as a single unit or alternatively multiple units can be mounted in a panel. Construction is from spun aluminium.
Standard finish is powder coat white while other finishes are available to suit the interior and architectural design requirements.
Model JAD - Sizes Available/Dimensions | ||||||
Size | Item # | ØN | ØF | H | M | T |
200 | 245291 | 198 | 264 | 92 | 33 | 15 |
250 | 245292 | 248 | 312 | 123 | 33 | 16 |
300 | 245293 | 295 | 375 | 149 | 40 | 18 |
350 | 245294 | 345 | 425 | 172 | 40 | 18 |
400 | 245295 | 395 | 495 | 179 | 50 | 18 |
500 | - | 495 | 595 | 248 | 50 | 26 |
600 | - | 595 | 715 | 300 | 60 | 30 |
Linear Slot Air Diffuser
Performance Data | ||||||||
Diffused Mode | ||||||||
SIZE (mm) | SELECTION PARAMETER | Neck Air Velocity | ||||||
1.5 | 2.0 | 2.5 | 3.0 | 3.5 | 4.0 | 5.0 | ||
200 | Airflow Rate (l/s) | 50 | 63 | 85 | 99 | 118 | 132 | 165 |
Throw (m) Min-Max | 2-3 | 2-4 | 3-5 | 4-6 | 5-6 | 5-7 | 6-10 | |
Pressure Loss (Pa) | 8 | 15 | 22 | 33 | 45 | 59 | 90 | |
NR Level | 18 | 26 | 30 | 35 | 45 | |||
250 | Airflow Rate (l/s) | 80 | 103 | 132 | 155 | 183 | 207 | 260 |
Throw (m) Min-Max | 2-4 | 3-5 | 4-6 | 5-7 | 6-9 | 7-11 | 8-13 | |
Pressure Loss (Pa) | 8 | 12 | 21 | 29 | 44 | 53 | 88 | |
NR Level | 23 | 28 | 34 | 38 | 46 | |||
300 | Airflow Rate (l/s) | 101 | 135 | 169 | 203 | 232 | 266 | 333 |
Throw (m) Min-Max | 2-5 | 5-7 | 8-9 | 10-11 | 12-14 | 14-16 | 16-17 | |
Pressure Loss (Pa) | 8 | 10 | 19 | 26 | 33 | 49 | 75 | |
NR Level | 24 | 28 | 34 | 38 | 47 | |||
350 | Airflow Rate (l/s) | 124 | 165 | 207 | 249 | 284 | 326 | 408 |
Throw (m) Min-Max | 3-5 | 6-7 | 8-10 | 10-12 | 13-15 | 16-17 | 18-20 | |
Pressure Loss (Pa) | 8 | 11 | 18 | 25 | 35 | 48 | 70 | |
NR Level | 25 | 28 | 34 | 38 | 48 | |||
400 | Airflow Rate (l/s) | 197 | 263 | 329 | 394 | 460 | 526 | 658 |
Throw (m) Min-Max | 3-6 | 5-8 | 10-11 | 11-13 | 14-15 | 16-18 | 19-21 | |
Pressure Loss (Pa) | 8 | 14 | 18 | 29 | 41 | 52 | 65 | |
NR Level | 28 | 35 | 40 | 43 | 50 | |||
500 | Airflow Rate (l/s) | 310 | 413 | 517 | 616 | 719 | 822 | |
Throw (m) Min-Max | 6-8 | 8-10 | 11-13 | 13-15 | 16-18 | 20-22 | ||
Pressure Loss (Pa) | 8 | 12 | 19 | 27 | 37 | 48 | ||
NR Level | 25 | 30 | 37 | 42 | 50 | |||
600 | Airflow Rate (l/s) | 446 | 592 | 743 | 888 | 1034 | 1184 | |
Throw (m) Min-Max | 6-9 | 11-13 | 15-18 | 19-21 | 21-23 | 24-27 | ||
Pressure Loss (Pa) | 9 | 13 | 21 | 27 | 43 | 48 | ||
NR Level | 25 | 32 | 39 | 45 | 54 |
Titus Linear Slot Diffuser
Performance Data | ||||||
Jet Mode | ||||||
SIZE (mm) | SELECTION PARAMETER | Neck Air Velocity | ||||
1.5 | 2.0 | 2.5 | 3.0 | 3.5 | 4.0 | 5.0 |
200 | Airflow Rate (l/s) | 50 | 63 | 85 | 99 | 118 |
Throw (m) Min-Max | 3-5 | 5-7 | 7-8 | 9-11 | 12-14 | |
Pressure Loss (Pa) | 19 | 27 | 48 | 68 | 85 | |
NR Level | 26 | 35 | 41 | 47 | ||
250 | Airflow Rate (l/s) | 80 | 103 | 132 | 155 | 183 |
Throw (m) Min-Max | 4-6 | 7-9 | 10-12 | 13-15 | 16-17 | |
Pressure Loss (Pa) | 19 | 31 | 50 | 60 | 70 | |
NR Level | 29 | 37 | 39 | 45 | ||
300 | Airflow Rate (l/s) | 101 | 135 | 169 | 203 | 232 |
Throw (m) Min-Max | 5-7 | 8-11 | 11-13 | 14-16 | 17-20 | |
Pressure Loss (Pa) | 12 | 22 | 31 | 40 | 62 | |
NR Level | 24 | 28 | 33 | 40 | ||
350 | Airflow Rate (l/s) | 124 | 165 | 207 | 249 | 284 |
Throw (m) Min-Max | 6-8 | 9-12 | 13-15 | 17-20 | 21-23 | |
Pressure Loss (Pa) | 11 | 23 | 35 | 46 | 70 | |
NR Level | 26 | 32 | 36 | 40 | ||
400 | Airflow Rate (l/s) | 197 | 263 | 329 | 394 | 460 |
Throw (m) Min-Max | 8-11 | 12-15 | 16-19 | 20-23 | 25-27 | |
Pressure Loss (Pa) | 13 | 23 | 39 | 53 | 75 | |
NR Level | 27 | 34 | 38 | 46 | ||
500 | Airflow Rate (l/s) | 310 | 413 | 517 | 616 | 719 |
Throw (m) Min-Max | 13-15 | 16-19 | 21-25 | 26-29 | 30-34 | |
Pressure Loss (Pa) | 13 | 23 | 37 | 50 | 70 | |
NR Level | 28 | 34 | 38 | 50 | ||
600 | Airflow Rate (l/s) | 446 | 592 | 743 | 888 | 1034 |
Throw (m) Min-Max | 14-17 | 19-22 | 23-26 | 28-31 | 33-38 | |
Pressure Loss (Pa) | 13 | 30 | 40 | 55 | 75 | |
NR Level | 32 | 38 | 44 | 53 |